Hardware-in-the-loop tests on distance protection considering VSC fault-ride-through control strategies
Jundi Jia1  Guangya Yang2 
[1] Center for Electric Power and Energy, Technical Univerisity of Denmark , Kgs. Lyngby , Denmark;Siemens A/S , Vejle , Denmark
关键词: converter-dominated power system;    converter current limit;    voltage source converter;    distance protection;    hardware-in-the-loop tests;    short-circuit response;    control parameters;    VSC fault-ride-through control strategies;    fault resistance;    unbalanced faults;    pre-fault power flow conditions;   
DOI  :  10.1049/joe.2018.0248
学科分类:工程和技术(综合)
来源: IET
PDF
【 摘 要 】

The short-circuit response of a voltage source converter (VSC) can vary from each other significantly with different control strategies. This study investigates the performance of distance protection under unbalanced faults considering two control strategies during fault-ride-through using hardware-in-the-loop tests. Variations on fault type, converter current limit, fault resistance and pre-fault power flow conditions are also examined. The tests reveal that the error in measured impedance caused by fault resistance will be enlarged in a converter-dominated power system. The first control strategy tends to cause overreach problem while the second can raise both overreach and underreach problems. The indeterminacy associated with the second strategy is jointly affected by control parameters, converter current limit, fault resistance and pre-fault power flow conditions. The findings of this study can help to stipulate grid requirements under unbalanced faults.

【 授权许可】

CC BY   

【 预 览 】
附件列表
Files Size Format View
RO201910254420131ZK.pdf 4850KB PDF download
  文献评价指标  
  下载次数:16次 浏览次数:24次