期刊论文详细信息
The Journal of Engineering
Analysis of the characteristics of fault-induced travelling waves in MMC-HVDC grid
Lanxi Tang1  Xinzhou Dong2 
[1] Department of Electrical Engineering, Tsinghua University , People's Republic of China
关键词: transmission line protection;    modular multilevel converter-based high-voltage direct current grid;    travelling wave protection;    DC circuit breaker;    fault-induced travelling waves;    fault information;    fault current;    MMC-HVDC grid;   
DOI  :  10.1049/joe.2018.0256
学科分类:工程和技术(综合)
来源: IET
PDF
【 摘 要 】

As the ability of DC circuit breaker is limited, transmission line protection has to identify the fault and inform the DC circuit breaker to cut off fault current as quickly as possible after a fault occurs on the transmission line of modular multilevel converter-based high-voltage direct current (MMC-HVDC) grid, in order to prevent the fault current from exceeding the ability of the DC circuit breaker. MMC-HVDC grid requires the speed of transmission line protection to be extremely fast. Travelling wave protection utilises the fault-induced travelling waves to construct protection criteria. As fault information firstly propagates in the form of travelling waves in the grid after a fault, travelling wave protection can achieve the fastest operation speed in theory, so it is an ideal choice for MMC-HVDC grid. This study analyses the characteristics of fault-induced travelling waves in the MMC-HVDC grid and the results can be the foundation of travelling wave protection of transmission line in MMC-HVDC grid.

【 授权许可】

CC BY   

【 预 览 】
附件列表
Files Size Format View
RO201910251924078ZK.pdf 1163KB PDF download
  文献评价指标  
  下载次数:12次 浏览次数:9次