期刊论文详细信息
The Journal of Engineering
Research on the fitting method to describe the mathematical expression of VFTO in GIS
  1    1    1 
[1] School of Automation, Wuhan University of Technology, Wuhan, Hubei, People's Republic of China;
关键词: overvoltage protection;    gas insulated switchgear;    EMTP;    transients;    power grids;    switchgear;    discharges (electric);    curve fitting;    VFTO impulse test;    standard VFTO waveform;    UHV GIS test platform;    fitting method;    mathematical expression;    electromagnetic transient phenomenon;    GIS insulation level;    power grid safety;    high-voltage equipment;    UHV disconnector operation;    SF6 gas discharge;    power–frequency waveform;    non-periodic impulse waveform;    ATP-EMTP software;   
DOI  :  10.1049/joe.2018.8753
来源: publisher
PDF
【 摘 要 】

Very fast transient over voltage (VFTO) is a unique electromagnetic transient phenomenon occurring in Gas Insulated Substation (GIS), which determines the insulation level of the GIS (above 330 kV). Unfortunately, up to the present, there is no standard VFTO waveform to test the high voltage equipment to ensure the safety of power grid. For this reason, this paper focuses on obtaining the standard VFTO waveform through finding a method to fit the curve of VFTO. Hence, a UHV disconnector operation experiment of GIS was carried out on the UHV GIS test platform. The representative waveform of VFTO generated by a single SF6 gas discharge was extracted from the measured data. Furthermore, The Fast Fourier Transformer is applied to analyze the frequency features of VFTO. As one of the switchgear operation voltage, VFTO can be concluded to be a superposition of the power-frequency waveform with the non-periodic impulse waveform. Thus, it is found that The Squares Method is convenient for fitting the expression of VFTO according to its transient characteristics. Then the standard VFTO waveform can be obtained from the fitting expression, which coincides well with the measured waveform. The simulation results using ATP-EMTP software are compared with the calculation results and the measured results.

【 授权许可】

CC BY   

【 预 览 】
附件列表
Files Size Format View
RO201910108719271ZK.pdf 2377KB PDF download
  文献评价指标  
  下载次数:10次 浏览次数:3次