期刊论文详细信息
The Journal of Engineering
Stability analysis of distributed generation grid-connected inverter
  1    1    1    1    1 
[1] Department of Electrical Engineering, Harbin Institute of Technology, Harbin, People's Republic of China;
关键词: invertors;    electric current control;    power grids;    distributed power generation;    phase locked loops;    power system stability;    linearisation techniques;    power system harmonics;    power grid system;    impedance mismatch;    small-signal model;    phase-locked loop;    current control;    inverter control system;    harmonic linearisation method;    inverter output impedance model;    grid impedance;    stability analysis method;    distributed generation grid-connected inverter;    distributed new energy power generation;    inverter main circuit average model;   
DOI  :  10.1049/joe.2018.8469
来源: publisher
PDF
【 摘 要 】

With the distributed new energy power generation increased, the power grid system becomes more and more complex, leading to its stability more likely to be affected. Among them, the resonance caused by impedance mismatch is particularly critical. The small-signal model of phase-locked loop and current control in the inverter control system have been established by using harmonic linearisation method. Combining the average model of inverter main circuit, the inverter output impedance model has been obtained. Using grid impedance and the inverter output impedance model, the stability analysis method based on impedance is used to analyse the influence of grid impedance on the stability of grid-connected inverters. Finally, the simulation proves the correctness of the analysis method.

【 授权许可】

CC BY   

【 预 览 】
附件列表
Files Size Format View
RO201910105279178ZK.pdf 2688KB PDF download
  文献评价指标  
  下载次数:12次 浏览次数:11次