期刊论文详细信息
Advances in Electrical and Computer Engineering
Energy Based Correlation Method for Location of Partial Discharge in Transformer Winding
JEYABALAN, V. ; USA, S..
关键词: transformers;    insulation failure;    partial discharge location;    energy;    correlation method;    time domain correlation;   
DOI  :  10.4316/AECE.2009.01008
学科分类:计算机科学(综合)
来源: Universitatea "Stefan cel Mare" din Suceava
PDF
【 摘 要 】

Partial discharge (PD) is the major source of insulation failure in power transformer. When transformers are subjected to electrical stress during operation, PD can occur. PD identification is an important diagnostic tool for the reliable operation of transformers. The PD signal detection and location is one of the main challenges for system utilities and equipment manufacturers. In this paper energy based correlation method is proposed for locating the source of PD for different pulse durations. Simulation and experiment are performed on lumped physical layer winding to prove the feasibility of the method and also verified with distributed model of 22kV prototype interleaved winding.