| The Journal of Engineering | |
| Performance analysis of automatic generation control of interconnected power systems with delayed mode operation of area control error | |
| Janardan Nanda1  Sukumar Mishra1  Dushyant Sharma1  | |
| [1] Department of Electrical Engineering, Indian Institute of Technology Delhi, Hauz Khas, New Delhi, India | |
| 关键词: area control error; wear reduction; hydro area; automatic generation control; thermal area; delayed mode operation; integral controllers; tear reduction; performance analysis; dynamic response; modified cost function; system performance improvement; interconnected power systems; step load perturbation; AGC; supplementary controller actuation; loading conditions; controller gain optimisation; particle swarm optimisation; | |
| DOI : 10.1049/joe.2015.0044 | |
| 学科分类:工程和技术(综合) | |
| 来源: IET | |
PDF
|
|
【 摘 要 】
This study presents automatic generation control (AGC) of interconnected power systems comprising of two thermal and one hydro area having integral controllers. Emphasis is given to a delay in the area control error for the actuation of the supplementary controller and to examine its impact on the dynamic response against no delay which is usually the practice. Analysis is based on 50% loading condition in all the areas. The system performance is examined considering 1% step load perturbation. Results reveal that delayed mode operation provides a better system dynamic performance compared with that obtained without delay and has several distinct merits for the governor. The delay is linked with reduction in wear and tear of the secondary controller and hence increases the life of the governor. The controller gains are optimised by particle swarm optimisation. The performance of delayed mode operation of AGC at other loading conditions is also analysed. An attempt has also been made to find the impact of weights for different components in a cost function used to optimise the controller gains. A modified cost function having different weights for different components when used for controller gain optimisation improves the system performance.
【 授权许可】
CC BY
【 预 览 】
| Files | Size | Format | View |
|---|---|---|---|
| RO201902024986661ZK.pdf | 848KB |
PDF