| 8th International Research-Technical Conference on the Problems of Designing, Construction and Use of Low Energy Housing | |
| Ice rink _ design of size of water storage tanks with small heat source for ice resurfacing machine | |
| 土木建筑工程 | |
| Kovac, M.^1 ; Kovacova, K.^1 | |
| Technical University of Kosice, Faculty of Civil Engineering, Vysokoskolska 4, Kosice | |
| 040 01, Slovakia^1 | |
| 关键词: Boiler room; Filling process; Heat sources; Investment costs; Storage tank; Thermal power; Water storage tanks; Water temperatures; | |
| Others : https://iopscience.iop.org/article/10.1088/1757-899X/415/1/012038/pdf DOI : 10.1088/1757-899X/415/1/012038 |
|
| 学科分类:土木及结构工程学 | |
| 来源: IOP | |
PDF
|
|
【 摘 要 】
The paper describes a method of design of storage tanks volume for an ice resurfacing machine in ice rink by using heat source with small thermal power (idea of downsizing). The main aim is to minimize investment costs for boiler room (the heat pump water-water). The achieved results show saving of investment costs about 35%. The request is the minimum water temperature at the value of 45°C before each filling process of resurfacing machine. Therefore it is very important to design the storage tanks volume where the water temperature will not be below the 45°C before the each filling an ice resurfacing machine during the hockey match or training. The required volume of storage tanks was calculated at the value of about 2000 litres if there is used the heat source with thermal power 45 kW. The number of storage tanks is given by boiler room dimensions too. In this case 3 storage tanks were designed.
【 预 览 】
| Files | Size | Format | View |
|---|---|---|---|
| Ice rink _ design of size of water storage tanks with small heat source for ice resurfacing machine | 295KB |
PDF