会议论文详细信息
International Symposium on Materials and Electrical Engineering 2017
Analysis of Transformer Conditions using Triangle Duval Method
材料科学;电工学
Permana, S.^1 ; Sumarto, S.^1 ; Saputra, W.S.^1
Department of Electrical Engineering Education, Universitas Pendidikan Indonesia, Dr. Setiabudhi Street No. 207, Bandung
40154, Indonesia^1
关键词: Dissolved gas;    Dissolved gas analyses (DGA);    Dissolved gases in oil;    Duval triangle methods;    Indonesia;    Thermal failure;   
Others  :  https://iopscience.iop.org/article/10.1088/1757-899X/384/1/012065/pdf
DOI  :  10.1088/1757-899X/384/1/012065
学科分类:材料科学(综合)
来源: IOP
PDF
【 摘 要 】

Electrical or thermal failure that occurred in the transformer oil can produce a dangerous gas called gas fault. By indicating the content of dissolved gases in the transformer oil, can be obtained information about what happened to the oil so it can be estimated indication of the type and cause of the failure in the transformer. The method used to identify and analyze the dissolved gases in oil is called Dissolved Gas Analysis (DGA). In this study conducted by the DGA Duval Triangle method for transformer oil used in geothermal power plant UPJP Kamojang PT. Indonesia Power. The results using Duval Triangle method produces thermal failure and partial discharge.

【 预 览 】
附件列表
Files Size Format View
Analysis of Transformer Conditions using Triangle Duval Method 799KB PDF download
  文献评价指标  