会议论文详细信息
2018 International Joint Conference on Materials Science and Mechanical Engineering
Reactive power characteristics analysis on emergency stop of doubly fed induction generator
Zhao, Yuting^1 ; Cui, Yang^1 ; Tang, Yaohua^2 ; Guo, Weimin^2
School of Electrical Engineering, Northeast Electric Power University, Jilin
132012, China^1
State Grid Henan Electric Power Research Institute Zhengzhou, Henan
450052, China^2
关键词: Asynchronous operation;    Crowbar protection;    Doubly fed induction generator (DFIG);    Doubly Fed Induction generators (DFIG);    Operating condition;    Power absorption;    Power characteristic;    Terminal voltages;   
Others  :  https://iopscience.iop.org/article/10.1088/1757-899X/383/1/012058/pdf
DOI  :  10.1088/1757-899X/383/1/012058
来源: IOP
PDF
【 摘 要 】

This paper analyzes the reactive power characteristics of the doubly-fed induction generator (DFIG) during the emergency off-grid process caused by the crowbar protection action. Since the action of the crowbar is much faster than the stator switching, the DFIG would be running with a short-term squirrel cage asynchronous operation. The mathematical model of the DFIG under above situation was proposed in this paper, based on which detailed analysis was given on reactive power demands during squirrel-cage asynchronous state of the DFIG. It is achieved that the amount of reactive power absorption was associated with the initial operating conditions such as the terminal voltage and speed before disconnection, which can be prescribed as the s-Q characteristic of DFIG. Finally, analysis on the measured data of the wind farm disconnected event verified the validity of the model.

【 预 览 】
附件列表
Files Size Format View
Reactive power characteristics analysis on emergency stop of doubly fed induction generator 708KB PDF download
  文献评价指标  
  下载次数:16次 浏览次数:40次