Optimization of 10 kW solar photovoltaic _ diesel generator hybrid energy system for different load factors at Jaisalmer location of Rajasthan, India
材料科学;机械制造;土木建筑工程
Saraswat, S.K.^1 ; Rao, K.V.S.^1
Department of Renewable Energy, Rajasthan Technical University, Kota, India^1
关键词: Bidirectional converter (BDC);    Diesel generators;    Hybrid energy system;    Levelized cost of electricities;    Rajasthan , India;    Solar insolation;    Solar photovoltaic panels;    Solar photovoltaics;   
Others  :  https://iopscience.iop.org/article/10.1088/1757-899X/330/1/012099/pdf
DOI  :  10.1088/1757-899X/330/1/012099
来源: IOP
PDF
【 摘 要 】
Jaisalmer town in Rajasthan, India is having annual average solar insolation of 5.80 kWh/m2/day and 270 - 300 clear sky days in a year. A 10 kW off-grid hybrid energy system (HES) consisting of solar photovoltaic panels - diesel generator - bidirectional converter and batteries with zero percentage loss of load for Jaisalmer is designed using HOMER (version 3.4.3) software. Different system load factors of 0.33, 0.50, 0.67, 0.83 and 1 corresponding to fraction of running hours per day of the system are considered. The system is analyzed for all three aspects, namely, electrical, economic and emission point of view. Least levelized cost of electricity (LCOE) of Rs. 8.43/kWh is obtained at a load factor value of 0.5. If diesel generator alone (without Solar PV) is used to fulfil the demand for a load factor of 0.5the value of LCOE is obtained Rs.19.23/kWh. Comparison of results obtained for HES and diesel generator are made for load factor of 0.5 and 1.
【 预 览 】
附件列表
Files Size Format View
Optimization of 10 kW solar photovoltaic _ diesel generator hybrid energy system for different load factors at Jaisalmer location of Rajasthan, India 839KB PDF download
  文献评价指标  
  下载次数:6次 浏览次数:17次