| Reliability Analysis of Differential Relay as Main Protection Transformer Using Fuzzy Logic Algorithm | |
| 工业技术;教育 | |
| Mulyadi, Y.^1 ; Sucita, T.^1 ; Sumarto^1 ; Alpani, M.^1 | |
| Department of Electrical Engineering Education, Universitas Pendidikan, Indonesia^1 | |
| 关键词: Differential relay; Electrical equipment; Electrical power system; Electricity supply; Fuzzy logic algorithms; Fuzzy logic system; Protection systems; Transmission line protection; | |
| Others : https://iopscience.iop.org/article/10.1088/1757-899X/306/1/012133/pdf DOI : 10.1088/1757-899X/306/1/012133 |
|
| 来源: IOP | |
PDF
|
|
【 摘 要 】
Electricity supply demand is increasing every year. It makes PT. PLN (Persero) is required to provide optimal customer service and satisfaction. Optimal service depends on the performance of the equipment of the power system owned, especially the transformer. Power transformer is an electrical equipment that transforms electricity from high voltage to low voltage or vice versa. However, in the electrical power system, is inseparable from interference included in the transformer. But, the disturbance can be minimized by the protection system. The main protection transformer is differential relays. Differential relays working system using Kirchoff law where inflows equal outflows. If there are excessive currents that interfere then the relays will work. But, the relay can also experience decreased performance. Therefore, this final project aims to analyze the reliability of the differential relay on the transformer in three different substations. Referring to the standard applied by the transmission line protection officer, the differential relay shall have slope characteristics of 30% in the first slope and 80% in the second slope when using two slopes and 80% when using one slope with an instant time and the corresponding ratio. So, the results obtained on the Siemens differential release have a reliable slope characteristic with a value of 30 on the fuzzy logic system. In a while, ABB a differential relay is only 80% reliable because two experiments are not reliable. For the time, all the differential relays are instant with a value of 0.06 on the fuzzy logic system. For ratios, the differential relays ABB have a better value than others brand with a value of 151 on the fuzzy logic system.
【 预 览 】
| Files | Size | Format | View |
|---|---|---|---|
| Reliability Analysis of Differential Relay as Main Protection Transformer Using Fuzzy Logic Algorithm | 996KB |
PDF