Cryogenic Engineering Conference 2017 | |
First operation of the XFEL linac with the 2 K cryogenic system | |
材料科学;物理学 | |
Paetzold, T.^2 ; Petersen, B.^1 ; Schnautz, T.^1 ; Ueresin, C.^1 ; Zajac, J.^3 | |
Deutsches Elektronen-Synchrotron (DESY), Hamburg, Germany^1 | |
Lindekryotechnik/Engie, Hamburg, Germany^2 | |
Lindekryotechnik, Pfungen, Switzerland^3 | |
关键词: Cold compressors; Control valves; Cryogenic system; Dynamic heat; Flow bypass; Helium II; Helium vapor; Mass flow; | |
Others : https://iopscience.iop.org/article/10.1088/1757-899X/278/1/012101/pdf DOI : 10.1088/1757-899X/278/1/012101 |
|
学科分类:材料科学(综合) | |
来源: IOP | |
【 摘 要 】
The RF operation of the about 800 superconducting 1.3 GHz 9-cell cavities of the XFEL linac requires helium II bath cooling at 2 K, corresponding to a vapor pressure of 3100 Pa. After the first cool-down of the XFEL linac to 4 K in December, 27th2016 the operation of the 2 K cryogenic system was started in January, 2nd2017. The 2 K cryogenic system consist of a 4-stage set of cold compressors to compress helium vapor at a mass flow of up to 100 g/s from 2400 Pa to about 110 kPa and a full flow bypass with an arrangement of heat exchangers and control valves. This paper describes the XFEL refrigerating plant, especially the 2 K cryogenic system, the tuning of the cold compressor regulation to adapt to the XFEL linac static and dynamic heat loads and experience of about 6 months of operation.
【 预 览 】
Files | Size | Format | View |
---|---|---|---|
First operation of the XFEL linac with the 2 K cryogenic system | 796KB | download |