Optimal placement of fast cut back units based on the theory of cellular automata and agent
航空航天工程;机械制造;无线电电子学
Yan, Jun^1 ; Yan, Feng^1
School of Electrical and Electronic Engineering, North China Electric Power University, Baoding, Hebei
071003, China^1
关键词: Auxiliary systems;    Determination methods;    Dispatching rules;    Grey relational analysis;    Network re-configuration;    Optimal placements;    Restoration process;    Thermal power generation;   
Others  :  https://iopscience.iop.org/article/10.1088/1757-899X/211/1/012028/pdf
DOI  :  10.1088/1757-899X/211/1/012028
学科分类:航空航天科学
来源: IOP
PDF
【 摘 要 】

The thermal power generation units with the function of fast cut back could serve power for auxiliary system and keep island operation after a major blackout, so they are excellent substitute for the traditional black-start power sources. Different placement schemes for FCB units have different influence on the subsequent restoration process. Considering the locality of the emergency dispatching rules, the unpredictability of specific dispatching instructions and unexpected situations like failure of transmission line energization, a novel deduction model for network reconfiguration based on the theory of cellular automata and agent is established. Several indexes are then defined for evaluating the placement schemes for FCB units. The attribute weights determination method based on subjective and objective integration and grey relational analysis are combinatorically used to determine the optimal placement scheme for FCB unit. The effectiveness of the proposed method is validated by the test results on the New England 10-unit 39-bus power system.

【 预 览 】
附件列表
Files Size Format View
Optimal placement of fast cut back units based on the theory of cellular automata and agent 250KB PDF download
  文献评价指标  
  下载次数:14次 浏览次数:35次