会议论文详细信息
2017 2nd Asia Conference on Power and Electrical Engineering
Analysis of SVC's Impact on Out-of-step Oscillation Based on Direct Method Considering Admittance Effect
能源学;电工学
He, Jing-Bo^1 ; Ding, Jian^2 ; Feng, Li^3 ; Ren, Jian-Wen^1 ; Tang, Wei^4 ; Yang, Cheng^4 ; Wang, Jing-Jin^4 ; Song, Yun-Ting^2
North China Electric Power University (Baoding), Baoding, Hebei
071003, China^1
China Electric Power Research Institute, Haidian District, Beijing
100085, China^2
State Grid Chongqin Electric Power Company, Yuzhong District, Chongqing
400015, China^3
State Grid Anhui Electric Power Company, Hefei, Anhui
230000, China^4
关键词: Dynamic characteristics;    Equal area criterion;    Grid structures;    Qualitative analysis;    Response speed;    Static VAR compensators (SVC);    System operation;    Variation pattern;   
Others  :  https://iopscience.iop.org/article/10.1088/1757-899X/199/1/012082/pdf
DOI  :  10.1088/1757-899X/199/1/012082
来源: IOP
PDF
【 摘 要 】

The widely employment of power electronic equipment in modern power system, may affect grid structure and system operation because of their diverse dynamic characteristics. In this paper, the impact of the static var compensators (SVC) on out-of-step oscillation is investigated based on the equal area criterion by considering SVC's admittance effect. Firstly, the variation pattern of bus voltage which is connected to SVC is concluded. Then the derivation of equation considering the admittance effect is given, which explains the ability of SVC to suppress out-of-step oscillation. SVC's impact on migration of out-of-step oscillation centre (OSOC) is discussed based on the expression of OSOC's electrical location. Moreover, the influence of SVC's response speed and capacity on its effect are presented by qualitative analysis. Finally, simulations on a two-end equivalent test system are carried out to verify the correctness of the theoretical analysis. It is found that the capacity and a response speed of SVC have significant effect on the out-of-step oscillation, while SVC have no d istinct influence on location of OSOC.

【 预 览 】
附件列表
Files Size Format View
Analysis of SVC's Impact on Out-of-step Oscillation Based on Direct Method Considering Admittance Effect 1457KB PDF download
  文献评价指标  
  下载次数:7次 浏览次数:20次