会议论文详细信息
2017 2nd Asia Conference on Power and Electrical Engineering
Simulation and Test Study on Very Fast Transient Overvoltage in 1000kV GIS Substation
能源学;电工学
Han, Bin^1 ; Lin, Jiming^1 ; Ban, Liangeng^1 ; Wang, Hao^1 ; Li, Zhibing^1 ; Xiang, Zutao^1
China Electric Power Research Institute, No.15 Xiaoying East Road, Haidian District, Beijing
100192, China^1
关键词: Commissioning test;    Damping resistors;    Disconnectors;    Gas insulated switchgear(GIS);    Operation mode;    Simulation model;    Switching operations;    Very fast transient over voltage (VFTO);   
Others  :  https://iopscience.iop.org/article/10.1088/1757-899X/199/1/012072/pdf
DOI  :  10.1088/1757-899X/199/1/012072
来源: IOP
PDF
【 摘 要 】

Disconnector switching in gas insulated switchgear (GIS) generates very fast transient overvoltage (VFTO). VFTO may damage the insulation of GIS equipment. This paper studies the VFTO of a 1000kV GIS substation. The simulation models are obtained according to the configuration of GIS. Operation modes of disconnector were summarized. The characteristics of VFTO were obtained. During the system commissioning test of the substation, VFTO were measured during disconnector switching. Comparison was made between the test and simulation results. The simulation results were in agreement with the test results. The accuracy of the simulation model is verified. Simulation and test study shows that it is safe to do switching operation of disconnector in this GIS substation without damping resistor.