Others  :  https://iopscience.iop.org/article/10.1088/1757-899X/177/1/012070/pdf
DOI  :  10.1088/1757-899X/177/1/012070
学科分类:计算机科学(综合)
来源: IOP
PDF
【 摘 要 】

Overvoltages occur in mine power supply systems during switching off consumers with high inductive load, such as transformers, reactors and electrical machines. Overvoltages lead to an increase of insulation degradation rate and may cause electric faults, power outage, fire and explosion of methane and coal dust. This paper is dedicated to simulation of vacuum circuit breaker switching overvoltages in a mine power supply system by means of Simulink MATLAB. The model of the vacuum circuit breaker implements simulation of transient recovery voltage, current chopping and an electric arc. Obtained results were compared to available experimental data.