会议论文详细信息
2016 2nd International Conference on Mechanical Engineering and Automation Science
Study of seismic response and vibration control of High voltage electrical equipment damper based on TMD
机械制造;无线电电子学
Liu, Chuncheng^1 ; Wang, Chongyang^1 ; Mao, Long^1 ; Zha, Chuanming^2
Northeast Dianli University Institute of Civil Engineering, Jilin, China^1
State Grid Xinjiang Economic Research Institute, Xinjiang, China^2
关键词: Damping coefficients;    Disconnecting switch;    Earthquake disaster;    Electrical equipment;    High voltage electrical equipment;    SF6 circuit breakers;    Three dimensional finite element model;    Tuned mass dampers;   
Others  :  https://iopscience.iop.org/article/10.1088/1757-899X/157/1/012027/pdf
DOI  :  10.1088/1757-899X/157/1/012027
来源: IOP
PDF
【 摘 要 】

Substation high voltage electrical equipment such as mutual inductor, circuit interrupter, disconnecting switch, etc., has played a key role in maintaining the normal operation of the power system. When the earthquake disaster, the electrical equipment of the porcelain in the transformer substation is the most easily to damage, causing great economic losses. In this paper, using the method of numerical analysis, the establishment of a typical high voltage electrical equipment of three dimensional finite element model, to study the seismic response of a typical SF6circuit breaker, at the same time, analysis and contrast the installation ring tuned mass damper (TMD damper for short), by changing the damper damping coefficient and the mass block, install annular TMD vibration control effect is studied. The results of the study for guiding the seismic design of high voltage electrical equipment to provide valuable reference.

【 预 览 】
附件列表
Files Size Format View
Study of seismic response and vibration control of High voltage electrical equipment damper based on TMD 1027KB PDF download
  文献评价指标  
  下载次数:29次 浏览次数:46次