会议论文详细信息
4th ModTech International Conference - Modern Technologies in Industrial Engineering
Investigation of the effect of packing location on performance of closed wet cooling tower based on exergy analysis
Qasim, S.M.^1 ; Hayder, M.J.^1
AL- Mustansiriya University College of Engineering, Baghdad, Iraq^1
关键词: Closed wet cooling towers;    Counter-flows;    Dry bulb temperature;    Exergy Analysis;    Exergy destructions;    Exergy efficiencies;    Thermal Performance;    Wet bulb temperature;   
Others  :  https://iopscience.iop.org/article/10.1088/1757-899X/145/3/032009/pdf
DOI  :  10.1088/1757-899X/145/3/032009
来源: IOP
PDF
【 摘 要 】

In this paper, the effect of packing location on thermal performance of Closed Wet Cooling Tower (CWCT) based on exergy analysis has been studied. The experimental study incorporates design, manufacture and testing of a modified counter flow forced draft CWCT prototype. The modification based on addition packing to the conventional CWCT. The variation of spray water temperature, air dry bulb temperature, air wet bulb temperature, enthalpy and relative humidity of air for different position along the tower are measured experimentally. Applying the exergy destruction method for the cooling tower; exergy destruction, exergy efficiency, exergy of water and air were calculated for two cases: CWCT with packing below the heat exchanger and CWCT with packing above the heat exchanger. It is highly important to analyze the exergy along the cooling tower height. Therefore, the exergy analysis of different elements along the height of the tower is carried out. Results show that the total exergy destruction of modified CWCT is higher when the heat exchanger is located above the packing at the highest point of the tower.

【 预 览 】
附件列表
Files Size Format View
Investigation of the effect of packing location on performance of closed wet cooling tower based on exergy analysis 1089KB PDF download
  文献评价指标  
  下载次数:11次 浏览次数:18次