8th Brazilian Congress on Metrology | |
DC resistance comparison between a current comparator bridge and the quantum Hall system at Inmetro | |
Da Silva, M.C.^1 ; Carvalho, H.R.^2 ; Vasconcellos, R.T.B.^1 | |
Electrical Standardization Metrology Laboratory, Inmetro, Duque de Caxias, Brazil^1 | |
Quantum Electrical Metrology Laboratory, Inmetro, Duque de Caxias, Brazil^2 | |
关键词: Bureau international des poids et mesures; Calibration system; Comparison result; Current comparators; Dc resistance; Electrical metrologies; K omegas; Quantum Hall systems; | |
Others : https://iopscience.iop.org/article/10.1088/1742-6596/733/1/012074/pdf DOI : 10.1088/1742-6596/733/1/012074 |
|
来源: IOP | |
【 摘 要 】
This paper presents a comparison results between the Quantum Hall System (QHS) under development at the Quantum Electrical Metrology Laboratory (Lameq) and the current comparator calibration system, traceable to the Bureau International des Poids et Mesures (BIPM), at the Electrical Standardization Metrology Laboratory (Lampe), both part of the Electrical Metrology Division, at Inmetro. Comparisons were performed with 1 Ω, 10 Ω, 100 Ω, 1 kΩ and 10 kΩ resistors. The results obtained over two years of work are presented here, showing that the comparison contributed to improve the calibration systems of both Lampe and Lameq.
【 预 览 】
Files | Size | Format | View |
---|---|---|---|
DC resistance comparison between a current comparator bridge and the quantum Hall system at Inmetro | 1157KB | download |