会议论文详细信息
2018 International Conference of Green Buildings and Environmental Management | |
Calculating the maximum penetration capacity of distributed generation considering current protection | |
土木建筑工程;生态环境科学 | |
Deng, Jingsong^1 ; Wang, Yingming^1 ; Sun, Difei^1 ; Zheng, Chenling^2 ; Yan, Hanting^2 ; Gao, Xiaojing^2 | |
Guangdong Power Grid Co. Ltd. Huizhou Power Supply Bureau, Huizhou | |
516003, China^1 | |
Guangzhou Power Electrical Technology Co. Ltd, Guangzhou | |
510640, China^2 | |
关键词: Inverter interfaced distributed generations; Iterative corrections; Low voltage ride through (LVRT); Non-linear relationships; Optimal allocation; Point of common coupling; Protection settings; Selectivity and sensitivity; | |
Others : https://iopscience.iop.org/article/10.1088/1755-1315/186/4/012034/pdf DOI : 10.1088/1755-1315/186/4/012034 |
|
来源: IOP | |
【 摘 要 】
With significant increasing penetration of the inverter interfaced distributed generations(IIDG), the radial network turns into a multipower-supply network. Working as an additional source, IIDG may increase the total fault level and altering the magnitude and direction of the fault current, which compromise the correct operation of the overcurrent protection system. This paper presents a new method to calculate the optimal allocation of IIDG without any amendment of protection settings, which will make great convenience for operators to review the accessible capacity of IIDG reported by users. Under the consideration of low voltage ride through(LVRT), the method uses iterative correction to figure out the nonlinear relationship between the fault current of IIDG and the fault voltage of the point of common coupling(PCC) in order to get the optimal capacity which meets the constraints of the current protection's selectivity and sensitivity.【 预 览 】
Files | Size | Format | View |
---|---|---|---|
Calculating the maximum penetration capacity of distributed generation considering current protection | 314KB | download |