【 摘 要 】

Transformer is an important equipment serving in power system. In this paper, the influence of metal particles on the electric field of transformer outlet device is studed via numerical simulation. The results reveal that the metal particles can increase the maximum field strength between the oil gap of the outlet device and the maximum field strength increases with the increase of the particle radius. The local field strength greater than the allowable oil gap may cause local micro-discharge. Metal particles in the alternating current field oscillation and discharge may be the bubble can make the electric field distortion, accelerate the process of insulation cracking and may further lead to insulation breakdown. By altering the oil gap width of outlet device, its insulation endurance can be improved under the influence of metallic particles.

【 预 览 】
附件列表
Files Size Format View
Influence of Metal Particles on the Electric Field Distribution of Outlet Device in a 500 kV Transformer 535KB PDF download
  文献评价指标  
  下载次数:12次 浏览次数:18次