会议论文详细信息
2nd International Symposium on Resource Exploration and Environmental Science
Rate-of-Current Based Protection for DC Distribution Network
生态环境科学
Ding, Fanfan^1 ; Zhang, Dahai^1 ; Zhang, Qiufang^1 ; Sheng, Wanxing^2 ; Wu, Ming^2 ; Song, Zhenhao^2
School of Electrical Engineering, Beijing Jiaotong University, Beijing
100044, China^1
China Electric Power Research Institute, Beijing
100192, China^2
关键词: Capacitor discharge;    Conventional currents;    Dc distribution;    DC distribution network;    Dc protections;    Protection criterion;    Response characteristic;    Transient process;   
Others  :  https://iopscience.iop.org/article/10.1088/1755-1315/170/4/042083/pdf
DOI  :  10.1088/1755-1315/170/4/042083
学科分类:环境科学(综合)
来源: IOP
PDF
【 摘 要 】

When fault occurs in the DC distribution network, the fault current rises rapidly, and it is difficult to develop fast and reliable relay protection. In the paper, by analyzing the response characteristics of each circuit when bipolar fault occurs in the DC distribution line, a fast DC protection scheme based on communication is proposed, which use the contrary change rate of current before and after the fault point during the transient process of capacitor discharge as the protection criterion. Finally, the feasibility of the proposed method is verified by simulation with PSCAD/EMTDC, and it proves the scheme has certain superiority, avoiding problems such as the setting and matching difficulties in conventional current protection methods.

【 预 览 】
附件列表
Files Size Format View
Rate-of-Current Based Protection for DC Distribution Network 241KB PDF download
  文献评价指标  
  下载次数:11次 浏览次数:11次