International Conference on Science, Infrastructure Technology and Regional Development (ICoSITeR) 2016 "Energy Security for Enhancing National Competitiveness" | |
Optimizing the Utility Power of a Geothermal Power Plant using Variable Frequency Drive (VFD) (Case Study: Sibayak Geothermal Power Plant) | |
能源学;经济学 | |
Sinaga, R.H.M.^1 ; Manik, Y.^1 | |
Engineering Management Study Program, Del Institute of Technology, Laguboti, Toba Samosir | |
22381, Indonesia^1 | |
关键词: Condenser pressure; Electricity companies; Engineering equation solvers; Geothermal; Sibayak; Variable frequency drives; Wet bulb temperature; Wet-bulb; | |
Others : https://iopscience.iop.org/article/10.1088/1755-1315/124/1/012007/pdf DOI : 10.1088/1755-1315/124/1/012007 |
|
来源: IOP | |
![]() |
【 摘 要 】
Sibayak Geothermal Power Plant (SGPP) is one of the plants being developed by Pertamina Geothermal Energy (PGE) at the upstream phase. At the downstream phase, State - owned Electricity Company (PLN) through PT. Dizamatra Powerindo is the developer. The gross capacity of the power plant is 13.3 MW, consisting 1 unit of Monoblock (2 MW) developed by PGE and 2 units (2×5.65 MW) operated through Energy Sales Contract by PLN. During the development phase of a geothermal power plant, there is a chance to reduce the utility power in order to increase the overall plant efficiency. Reducing the utility power can be attempted by utilizing the wet bulb temperature fluctuation. In this study, a modeling process is developed by using Engineering Equation Solver (EES) software version 9.430. The possibility of energy saving is indicated by condenser pressure changes as a result of wet bulb temperature fluctuation. The result of this study indicates that the change of condenser pressure is about 50.8% on the constant liquid/gas (L/G) condition of the wet bulb temperature of 15°C to 25°C. Further result indicates that in this power plant, Cooling Tower Fan (CTF) is the facility that has the greatest utility load, followed by Hot Well Pump (HWP). The saving of the greatest utility load is applied trough Variable Frequency Drive (VFD) instrumentation. The result of this modeling has been validated by actual operations data (log sheet). The developed model has also been reviewed trough Specific Steam Consumption (SSC), resulting that constant L/G condition allows the optimum condition on of the wet bulb temperature of 15°C to 25°C.
【 预 览 】
Files | Size | Format | View |
---|---|---|---|
Optimizing the Utility Power of a Geothermal Power Plant using Variable Frequency Drive (VFD) (Case Study: Sibayak Geothermal Power Plant) | 353KB | ![]() |