会议论文详细信息
International Conference on Environment and Technology 2017
Reconstruction of Power Supply System 20 kV Distribution to Compare Power Rate and Fall Voltage PT. PLN (Persero) Area Dumai
生态环境科学
Tanjung, Abrar^1 ; Monice, M.^1
University Lancang Kuning, Pekanbaru
28265, Indonesia^1
关键词: feeder 20 kV;    Power-losses;    reconfiguration;    substation;    Voltage drop;   
Others  :  https://iopscience.iop.org/article/10.1088/1755-1315/97/1/012048/pdf
DOI  :  10.1088/1755-1315/97/1/012048
学科分类:环境科学(综合)
来源: IOP
PDF
【 摘 要 】

Electricity in Bagan Siapi city fire is channeled through a feeder distribution system of 20 kV. The main supply of Bagan Siapi-api city comes from PLTD unit Bagan Siapi fire which is A ± 1.5 kms from the load center and Duri Substation is A ± 102 kms from Bagan Siapi-api city through Hubung Ujung Tanjung. The long distances between the Duri Mainstation and Bagan Siapiapi city resulted in a 14.85 kV end-voltage and a 988.7 kW loss. Voltage losses resulted in ineffective service to the consumer and large network power losses being uneconomical for power delivery operations. The result of end voltage calculation is 10.42 kV and the power loss is 988.7 kW. After the New Substation operates, reconfiguration-1 produces the lowest end-voltage calculation of 16.21 kV and a power loss of 136.59 kW, while reconfiguration-2 produces a low end stress calculation of 17.37 kV and a power loss of 56.93 kW.

【 预 览 】
附件列表
Files Size Format View
Reconstruction of Power Supply System 20 kV Distribution to Compare Power Rate and Fall Voltage PT. PLN (Persero) Area Dumai 255KB PDF download
  文献评价指标  
  下载次数:13次 浏览次数:35次