会议论文详细信息
2017 3rd International Conference on Energy, Environment and Materials Science
Study of comparison between Ultra-high Frequency (UHF) method and ultrasonic method on PD detection for GIS
能源学;生态环境科学;材料科学
Li, Yanran^1 ; Chen, Duo^1 ; Li, Li^1 ; Zhang, Jiwei^1 ; Li, Guang^1 ; Liu, Hongxia^1
Jinan Power-supply Company, Jinan, Shandong
250012, China^1
关键词: Fault localization;    GIS-Gas insulated switchgear;    Insulation performance;    Partial discharge detection;    Partial discharge in GIS;    Partial discharge tests;    Simulated environment;    Ultra high frequency method;   
Others  :  https://iopscience.iop.org/article/10.1088/1755-1315/94/1/012086/pdf
DOI  :  10.1088/1755-1315/94/1/012086
来源: IOP
PDF
【 摘 要 】

GIS (gas insulated switchgear), is an important equipment in power system. Partial discharge plays an important role in detecting the insulation performance of GIS. UHF method and ultrasonic method frequently used in partial discharge (PD) detection for GIS. However, few studies have been conducted on comparison of this two methods. From the view point of safety, it is necessary to investigate UHF method and ultrasonic method for partial discharge in GIS. This paper presents study aimed at clarifying the effect of UHF method and ultrasonic method for partial discharge caused by free metal particles in GIS. Partial discharge tests were performed in laboratory simulated environment. Obtained results show the ability of anti-interference of signal detection and the accuracy of fault localization for UHF method and ultrasonic method. A new method based on UHF method and ultrasonic method of PD detection for GIS is proposed in order to greatly enhance the ability of anti-interference of signal detection and the accuracy of detection localization.

【 预 览 】
附件列表
Files Size Format View
Study of comparison between Ultra-high Frequency (UHF) method and ultrasonic method on PD detection for GIS 279KB PDF download
  文献评价指标  
  下载次数:13次 浏览次数:46次