2017 International Conference on Sustainable Development on Energy and Environment Protection | |
On Fusing Mechanism Involving the Fuses at Secondary Winding of PT Induced by VFTO | |
能源学;生态环境科学 | |
Ma, X.H.^1 ; Han, S.^3 ; Hu, Z.^3 ; Huang, J.K.^2 ; Liu, X.B.^3 | |
Nano/micro Science and Technology Center, School of Mechanical Engineering, Jiangsu University, Zhenjiang | |
212013, China^1 | |
Guizhou Electric Power Research Institute, Guizhou, China^2 | |
Department of Electrical Engineering, Guizhou University, Guizhou, China^3 | |
关键词: Current distribution; High-frequency voltage; Parallel arrangement; Secondary circuit; Secondary equipments; Secondary windings; Three-phase equivalent models; Very fast transient over voltage (VFTO); | |
Others : https://iopscience.iop.org/article/10.1088/1755-1315/86/1/012032/pdf DOI : 10.1088/1755-1315/86/1/012032 |
|
学科分类:环境科学(综合) | |
来源: IOP | |
【 摘 要 】
The impact of very fast transient over-voltage(VFTO) on the primary and secondary equipment in gas insulated station(GIS) should not be ignored. In this paper, the research on fusing mechanism involving the fuses at secondary winding of PT induced by VFTO is carried out based on an actual case from the 500kV GIS substation belonged to Guizhou Tianshengqiao No.2 hydro power plant. As for the high voltage side, the transfer function about over-voltage can be formed in order to analyse the characteristics about high frequency over-voltage. As for the low voltage side, a three-phase equivalent model for secondary circuit of PT with the parallel arrangement at the A, B and C phases may be built for simulating the current distribution of the low voltage fuses in the situation of high frequency voltage and current. The results show that the maximum allowable current of fuse might be reduced greatly in the high-frequency circumstance due to skin effect and proximity effect, in comparison with nominal frequency condition.