会议论文详细信息
2019 2nd International Conference of Green Buildings and Environmental Management | |
Effect of groove defect State on propagation of SH0 guided wave in flat steel of grounding network | |
生态环境科学 | |
Ke-Long, H.E.^1 ; Zhang, Zhou-Quan^2 ; Zhuan, L.I.U.^2 ; Hui, Z.H.U.^1 ; Peng, Guo-Da^1 ; Zhan, T.U.^1 | |
Nanchang Kechen Electric Power Test and Research Co., Ltd, Nanchang | |
330096, China^1 | |
State Grid Jiangxi Electric Power Research Institute, Nanchang | |
330096, China^2 | |
关键词: Cross sectional area; Defect detection; Echo signals; Groove defect; Grounding network; Propagation process; Reflection waves; Substation grounding; | |
Others : https://iopscience.iop.org/article/10.1088/1755-1315/310/3/032019/pdf DOI : 10.1088/1755-1315/310/3/032019 |
|
学科分类:环境科学(综合) | |
来源: IOP | |
【 摘 要 】
By studying the depth and length of groove defect, this paper explores its effect on the propagation of SH0 wave in the flat steel of substation grounding network. The results show that the sensitivity of SH0 wave to defect detection in the propagation process depends on the depth of defect, that is, the corrosion cross-sectional area. Reflection waves are difficult to detect when the defect cross-sectional area is less than 18.75%. The smaller the defect depth, the weaker the echo signal.
【 预 览 】
Files | Size | Format | View |
---|---|---|---|
Effect of groove defect State on propagation of SH0 guided wave in flat steel of grounding network | 709KB | download |