会议论文详细信息
3rd International Symposium on Resource Exploration and Environmental Science
Adaptive Dynamic Grid Partitioning for Reactive-Power/Voltage Control Based on Secondary Voltage Control
生态环境科学
Li, Tie^1 ; Liang, Xiaohe^1 ; Jiang, Feng^1 ; Feng, Zhanwen^1 ; Zhang, Kai^1 ; Cai, Zhuang^1 ; Gong, Xiaowei^2 ; Bai, Xue^2 ; Li, Mingzhu^2
State Grid Liaoning Electric Power Supply Co. Ltd., Shenyang
110006, China^1
Electric Power Research Institute of State Grid Liaoning Electric Power Supply Co. Ltd., Shenyang
110006, China^2
关键词: Adaptive dynamics;    Current status;    Load node;    Operating condition;    Optimal partitions;    Secondary voltage control;   
Others  :  https://iopscience.iop.org/article/10.1088/1755-1315/300/4/042109/pdf
DOI  :  10.1088/1755-1315/300/4/042109
学科分类:环境科学(综合)
来源: IOP
PDF
【 摘 要 】

Reactive power voltage partition control is an important part of AVC secondary voltage control. Aiming at the current status of secondary voltage control, based on the voltage/reactive sensitivity and modularity function, an adaptive dynamic partitioning method is proposed, which changes with the operating conditions of the grid. With each reactive power source partition center, the load nodes are mapped to the corresponding reactive power sources according to the voltage/reactive sensitivity, and the regional merging automatically forms the optimal partition by using the modularity function as a measure. Finally, the proposed method is verified by the IEEE-39 system.

【 预 览 】
附件列表
Files Size Format View
Adaptive Dynamic Grid Partitioning for Reactive-Power/Voltage Control Based on Secondary Voltage Control 307KB PDF download
  文献评价指标  
  下载次数:15次 浏览次数:22次