Hybrid Modeling of Central Air-Conditioning Cold Source System Energy Consumption with K-means Cluster Algorithm
能源学;生态环境科学
Zhou, Zhihao^1
School of Energy and Environment, Southeast University, Nanjing
210096, China^1
关键词: Artificial neural network models;    Central air-conditioning;    Energy consumption prediction;    Gray-box models;    Prediction accuracy;    Simulation data;    Source systems;    System operation;   
Others  :  https://iopscience.iop.org/article/10.1088/1755-1315/295/5/052035/pdf
DOI  :  10.1088/1755-1315/295/5/052035
学科分类:环境科学(综合)
来源: IOP
PDF
【 摘 要 】

Gray box model and artificial neural network (ANN) model of central air-conditioning cold source system have been established with simulation data to predict system operation energy consumption and compare the prediction accuracy difference of models under variable training data. A hybrid model is proposed to combine gray box model and ANN model based on K-means cluster algorithm. The results show that ANN model has higher prediction accuracy than gray box model when the membership of model input variables to trained input data is greater than 0.4. Otherwise, the gray box model has higher energy consumption prediction accuracy. Compared with gray box model and ANN model, prediction accuracy of hybrid model increases 27.7% and 33.85% on average under different training data.

【 预 览 】
附件列表
Files Size Format View
Hybrid Modeling of Central Air-Conditioning Cold Source System Energy Consumption with K-means Cluster Algorithm 638KB PDF download
  文献评价指标  