会议论文详细信息
2019 5th International Conference on Energy Materials and Environment Engineering
The method of leaking detection which adopts Infrared imaging and infrared absorption joint positioning and its application
能源学;生态环境科学
Lin, Fu-Hai^1^2 ; Tu, Zhan^1
Nanchang Kechen Electric Power Test and Research Co. Ltd, Nanchang, Jiangxi
330096, China^1
State Grid Jiangxi Electric Power Research Institute, Nanchang, Jiangxi
330096, China^2
关键词: Charged state;    Current practices;    Field of measurements;    Infrared absorption method;    ITS applications;    Leaking position;    Power industry;    Substation equipment;   
Others  :  https://iopscience.iop.org/article/10.1088/1755-1315/295/3/032012/pdf
DOI  :  10.1088/1755-1315/295/3/032012
学科分类:环境科学(综合)
来源: IOP
PDF
【 摘 要 】

In order to measure the leakage of substation equipment's SF6 gas in the charged state, the current practice is the single infrared imaging in the power industry. But there are different factors such as wind speed, leak detection position, leak imaging can only be seen a flat area on the graph, not accurate positioning. The method in this paper is to joint spot and side, and first with infrared imaging legal out a flat area roughly, then gradually narrowed the leaking range by infrared absorption method, until the biggest SF6 gas density is detected, and it is just the leaking position. The method in the gas leakage detection of GIS substation charged is prevalent. The article has carried on the thorough analysis to the technology and successfully applied to the field of measurement.

【 预 览 】
附件列表
Files Size Format View
The method of leaking detection which adopts Infrared imaging and infrared absorption joint positioning and its application 649KB PDF download
  文献评价指标  