会议论文详细信息
International Scientific and Practical Conference: Water Power Energy Forum 2018
Selection of optimum inclination angle of a nozzle at circulatory heating of fuel oil in the RVS-3000 tank
Kamalov, R.F.^1 ; Karaeva, J.V.^1 ; Vildanov, R.R.^2
Institute of Power Engineering and Advanced Technologies - Subdivision, Federal Research Center Kazan Scientific Center, Russian Academy of Sciences, 2/31 Lobachevsky str., Kazan
420111, Russia^1
Federal State Budgetary Educational Institution of Higher Education, Kazan State Power Engineering University, 51 Krasnoselskaya str., Kazan
420066, Russia^2
关键词: Fuel temperature;    Heating time;    Inclination angles;    Storage periods;    Storage temperatures;   
Others  :  https://iopscience.iop.org/article/10.1088/1755-1315/288/1/012095/pdf
DOI  :  10.1088/1755-1315/288/1/012095
来源: IOP
PDF
【 摘 要 】

The paper presents the mathematical model and the numerical studies results of heat transfer and hydrodynamics at circulatory heating of the M100 fuel oil in the RVS-3000 tank. Calculations for various inclination angles of the nozzle in the range of 40° to -40° in increments of 10° were made. The winter storage period of fuel oil in the fuel tank is considered. Comparison of the tank heating time up to the hot storage temperature (60°C) and up to the fuel temperature before feeding to the nozzles for combustion (90°C) is performed.

【 预 览 】
附件列表
Files Size Format View
Selection of optimum inclination angle of a nozzle at circulatory heating of fuel oil in the RVS-3000 tank 469KB PDF download
  文献评价指标  