4th Asia Conference of International Building Performance Simulation Association | |
Dynamic simulation of a VAV system based on dynamic PMV control | |
土木建筑工程 | |
Li, H.^1^2 ; Shan, M.Z.^1^2 ; Yu, Y.^1^2 ; Duan, P.Y.^3 | |
Key Laboratory of Renewable Energy Technologies for Buildings, Ministrytract of Education, Jinan | |
250101, China^1 | |
School of Thermal Engineering, Shandong Jianzhu University, Jinan | |
250101, China^2 | |
Shandong Normal University, Jinan | |
250101, China^3 | |
关键词: Constant temperature control; Indoor thermal environments; Predicted mean vote; Questionnaire surveys; Simulation model; Transient systems; Variable air volume; VAV air conditioning systems; | |
Others : https://iopscience.iop.org/article/10.1088/1755-1315/238/1/012053/pdf DOI : 10.1088/1755-1315/238/1/012053 |
|
学科分类:土木及结构工程学 | |
来源: IOP | |
【 摘 要 】
The predicted mean vote (PMV) index is taken as the control target in an air-conditioning system is in line with the requirements of the indoor thermal environment. In addition, with the emergence of "air conditioning disease", people began to pay more attention to the study on the dynamic thermal comfort of indoor thermal environment. Firstly, the dynamic PMV is proposed, and the amplitude and period of the dynamic PMV are confirmed by experiments and questionnaire surveys. Then, a simulation model of variable air volume (VAV) air-conditioning system based on dynamic PMV control is built by Transient System Simulation Program (TRNSYS). Simultaneously, the simulation models of the VAV air-conditioning system based on constant temperature control and static PMV control are also built by TRNSYS. The simulation results show that the comfort and energy saving of the VAV air-conditioning system based on dynamic PMV control are more prominent.
【 预 览 】
Files | Size | Format | View |
---|---|---|---|
Dynamic simulation of a VAV system based on dynamic PMV control | 777KB | download |