Security Monitoring of Railway Power Cable Joints Based on AD7606 AC Synchronization Sampling
Liu, Jiajun^1 ; Du, Zhiliang^1
Institute of Water Resources and Hydro-Electric, Xi'An University of Technology, Xi'an
710048, China^1
关键词: Asynchronous sampling;    Frequency correction;    On-line monitoring device;    Potential transformer;    Real time monitoring;    Security monitoring;    Synchronization circuits;    Synchronous sampling;   
Others  :  https://iopscience.iop.org/article/10.1088/1757-899X/569/3/032048/pdf
DOI  :  10.1088/1757-899X/569/3/032048
来源: IOP
PDF
【 摘 要 】

To avoid the frequent accident of burning loss of railway 10kV power cable joints, an online monitoring device is developed based on tanδ, the tangential value of loss angle of the cable's main insulation, and other state variables, to carry out real-time monitoring and safety evaluation of the cable's running state, so as to timely alarm and predict hidden accident danger for abnormal cable joints. The measurement of tanδ adopts a frequency correction method based on AD7606 AC synchronous sampling and FFT phase difference frequency correction, which can avoid the spectrum leakage effect of asynchronous sampling and the phase-locked loop synchronization circuit with complicated cost. This paper regards the current source of grounding wire of railway cable when no electric locomotive passes through the railway electrical section as leakage current of the main insulation of cable. Tanδ is monitored by collecting and processing the voltage of cable bus-bar potential transformer and the current of cable grounded wire.

【 预 览 】
附件列表
Files Size Format View
Security Monitoring of Railway Power Cable Joints Based on AD7606 AC Synchronization Sampling 658KB PDF download
  文献评价指标  
  下载次数:16次 浏览次数:20次