会议论文详细信息
2019 The 5th International Conference on Electrical Engineering, Control and Robotics
A New Principle of Breaker Failure Protection Based on Station Information Sharing
无线电电子学;计算机科学
Pan, Yong^1 ; Han, Wei^1 ; Geng, Jinfeng^1 ; Liu, Yao^1
Electrical Power Research Institute of Henan Electric Power Company, Zhengzhou
450052, China^1
关键词: Analysis and simulation;    Breaker failure protection;    Circuit breaker failures;    Current detection;    Failure protection;    High reliability;    Information sharing;    Protection criterion;   
Others  :  https://iopscience.iop.org/article/10.1088/1757-899X/533/1/012041/pdf
DOI  :  10.1088/1757-899X/533/1/012041
学科分类:计算机科学(综合)
来源: IOP
PDF
【 摘 要 】

In the case of terminal fault of long line, the failure protection of traditional circuit breaker has the problem of refusing to operate due to the insufficient sensitivity of voltage locking elements. A new circuit breaker failure protection scheme based on station area information sharing is proposed in this paper. The new scheme will replace the protection export signal with the actual protection criterion. In addition, it sets up two current transformers to detect whether the breaker is cut off after the circuit breaker is cut off, and checks the redundant current of the bus, which can improve the accuracy of the current detection. Besides, it uses reclosing checkout voltage device signal to supplement the original compound blocking signal. Theoretical analysis and simulation results show that the scheme can effectively cover the full length of the transmission line and has high reliability.

【 预 览 】
附件列表
Files Size Format View
A New Principle of Breaker Failure Protection Based on Station Information Sharing 710KB PDF download
  文献评价指标  
  下载次数:10次 浏览次数:39次