2019 The 5th International Conference on Electrical Engineering, Control and Robotics | |
Research on Distributed Protection in Switch Stations Based on GOOSE | |
无线电电子学;计算机科学 | |
Jiang, Xin^1 ; Yun, Baoji^1 | |
Electrical Engineering, Electrical Engineering Department, Xi'An University of Science and Technology, 710054, China^1 | |
关键词: Automatic transfer switches; Distributed voltages; IEC61850 standard; Network communications; Protection function; Protection logic; Secondary protection; Switching stations; | |
Others : https://iopscience.iop.org/article/10.1088/1757-899X/533/1/012002/pdf DOI : 10.1088/1757-899X/533/1/012002 |
|
学科分类:计算机科学(综合) | |
来源: IOP | |
【 摘 要 】
The application of IEC61850 standard and the development of smart terminal unit (STU) technology provide a powerful platform for secondary protection research of distribution network. Aiming at the problems of override trip in the protection of the incoming line and feeders on traditional 10kV switching stations, a scheme combining distributed voltage loss protection and overcurrent protection is proposed. The smart terminal unit collects and processes the operation data, realizes data exchange through GOOSE network communication, and cooperates to realize the protection function of the switch stations. In this paper, a protection logic diagram based on the GOOSE mechanism is constructed, which realizes the protection function of feeder lines fault lockout incoming line breakers and the bus line fault lockout busbar automatic transfer switch.
【 预 览 】
Files | Size | Format | View |
---|---|---|---|
Research on Distributed Protection in Switch Stations Based on GOOSE | 1023KB | download |