会议论文详细信息
27th International Cryogenics Engineering Conference and International Cryogenic Materials Conference 2018
Improvement of cooling capacity of 4K GM cryocooler in magnetic fields
Morie, Takaaki^1 ; Shiraishi, Taisuke^2 ; Mizuno, Yoji^2 ; Xu, Mingyao^2
Technology Research Center, Sumitomo Heavy Industries Ltd., 19 Natsushima-cho, Yokosuka-city, Kanagawa
237-8555, Japan^1
Precision Equipment Group, Sumitomo Heavy Industries Ltd., 2-1-1 Yato-cho, Nishitokyo-city, Tokyo
188-8585, Japan^2
关键词: A-stable;    Cooling Capacity;    Cryocoolers;    Exposed to;    G-m cryocooler;    High capacity;    Sumitomo heavy industries;   
Others  :  https://iopscience.iop.org/article/10.1088/1757-899X/502/1/012036/pdf
DOI  :  10.1088/1757-899X/502/1/012036
来源: IOP
PDF
【 摘 要 】
4K GM cryocoolers have been widely used for cooling superconducting magnets, such as, magnets in MRI, NMR, Magnetic field-Applied Czochralski (MCZ) and electron accelerator systems. In general, high capacity cryocoolers are required to maintain a stable operation for these systems. Cryocoolers are inevitably exposed to the magnetic fields in these superconducting magnet systems. Therefore, it is important that the cooling capacity can be maintained in magnetic fields. Recently, we measured the cooling capacity of a Sumitomo Heavy Industries, Ltd., (SHI) new 4K GM cryocooler, RDE-412, in magnetic fields up to 3.0 T. It is found that the second stage temperature only increases about 0.3 K and the cooling capacity keeps in the specification of 1.25 W at 4.0 K up to 3.0 T.