会议论文详细信息
2019 4th Asia Conference on Power and Electrical Engineering
Research on Key Technical Parameters of 1100kV Live Tank Circuit Breaker for UHVDC Converter Station
能源学;电工学
Du, Ning^1 ; Xiang, Zutao^1 ; Han, Bin^1 ; Yang, Yue^1 ; Xiang, Changyuan^1
State Key Laboratory of Power Grid Safety and Energy Conservation, China Electric Power Research Institute, No. 15, Xiaoying east road, Qinghe, Haidian district, Beijing, China^1
关键词: AC-grid;    Converter station;    In-rush current;    Tank circuits;    Transient recovery voltage;    UHVDC transmission;   
Others  :  https://iopscience.iop.org/article/10.1088/1757-899X/486/1/012007/pdf
DOI  :  10.1088/1757-899X/486/1/012007
来源: IOP
PDF
【 摘 要 】

Many of UHVDC transmission projects planned and under construction are hierarchical connected to 500kV and 1000kV AC grid in China. Live tank circuit breakers are selected for switching 1000kV filters. During the development of 1100kV live tank circuit breakers, the closing inrush current and transient recovery voltage are key factors for structure of extinguishing chamber of circuit breakers. In this paper, the above factors are analyzed by simulation, and key technical parameters of 1100kV live tank circuit breakers for UHVDC converter station are proposed.

【 预 览 】
附件列表
Files Size Format View
Research on Key Technical Parameters of 1100kV Live Tank Circuit Breaker for UHVDC Converter Station 393KB PDF download
  文献评价指标  
  下载次数:5次 浏览次数:25次