会议论文详细信息
1st International Conference on Advanced Engineering and Technology
Experimental Study of The Performance Characteristic an Induced Draft Cooling Tower with Variates Fillings
工业技术(总论)
Novianarenti, E.^1^2 ; Setyono, G.^1^3 ; Safitra, A.G.^4
Mechanical Engineering Department, Adhi Tama Institute of Technology, Surabaya, Indonesia^1
Fluid Mechanics and Thermal Laboratory, Adhi Tama Institute of Technology, Surabaya, Indonesia^2
Internal Combustion Engine Laboratory, Adhi Tama Institute of Technology, Surabaya, Indonesia^3
Engineering Mechanics and Energy, Electronics Engineering, Polytechnic Institute of Surabaya, Indonesia^4
关键词: Contact surface;    Contact time;    Controlling parameters;    Heat and mass transfer coefficients;    Heat transfer correlation;    Hot water;    Induced drafts;    Performance characteristics;   
Others  :  https://iopscience.iop.org/article/10.1088/1757-899X/462/1/012027/pdf
DOI  :  10.1088/1757-899X/462/1/012027
学科分类:工业工程学
来源: IOP
PDF
【 摘 要 】
The aim of this research is designing and testing an Induced Draft Cooling Tower (IDCT). The Cooling tower is the main instrument which used to cool the hot water from the condenser and release heat into the atmosphere at a power plant. Temperature is maintaining as cool as original condition. One of the components of the cooling tower is filler. It is very influential on IDCT performance, where the contact surface between water and air is expanded and the contact time is extended. An experimental study to evaluated the heat and mass transfer coefficient is conducted. A heat transfer correlation is developed; a new variable is defined. The effect of controlling parameters such as range of temperature, heat rejected rates, effectiveness has been analysed. IDCT was filled with a straight, zigzag and wave filler. The results indicate that the tower characteristics increase with increase cold air velocity, with the variation of filler, the highest tower characteristics get from wave filler arrangement.
【 预 览 】
附件列表
Files Size Format View
Experimental Study of The Performance Characteristic an Induced Draft Cooling Tower with Variates Fillings 598KB PDF download
  文献评价指标  
  下载次数:4次 浏览次数:18次